| 2014-01-31 16:07:06 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | PROPOSED ADDITION AND AREA BEING CONVERTED TO HABITABLE |
| | SPACE AS REQUIRED BY THE 2010 FBC ENERGY CONSERVATION. |
| | THE ENERGY FORMS ARE REQUIRED TO BE SIGNED BY THE |
| | PREPARER AND THE OWNER/AGENT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |
| | |
| | |
| | NOTE: |
| | THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA, DESIGNATED FLOOD ZONE A5. THE MINIMUM ELEVATION |
| | IS 7 FEET BFE PLUS THE ADDITIONAL 6" OF FREEBOARD |
| | REQUIRED BY CITY ORDINANCE. BASED ON CITY BUILDING |
| | DEPARTMENT RECORDS THE CUMULATIVE TOTAL COSTS OF WORK |
| | ON THIS BUILDING INCLUDING $32,000.00 FOR THE PROPOSED |
| | WORK IS $ 105,889.00. THE CONTRACTOR SUBMITTED AN |
| | APPRAISAL FROM CHARLEEN MCMANUS, SRA, OF ANDERSON & |
| | CARR, INC. STATING THE MARKET VALUE OF THE BUILDING |
| | IMPROVEMENTS TO BE $ 320,000.00. BECAUSE THE TOTAL OF |
| | PREVIOUS IMPROVEMENTS AND THE PROPOSED WORK IS LESS |
| | THAN 50 PERCENT OF THE MARKET VALUE, THIS IS NOT |
| | CONSIDERED A SUBSTANTIAL IMPROVEMENT. ACCORDING TO THE |
| | PROPERTY APPRAISER'S RECORDS THE STRUCTURE WAS BUILT IN |
| | 1935 AND HAS HAD NO SUBSTANTIAL IMPROVEMENTS PRIOR TO |
| | THE DATE OF THE INITIAL FIRM (MARCH 1, 1979) . |
| | THEREFORE THIS IS BUILDING IS CONSIDERED TO BE |
| | PRE-FIRM. BASED ON TABLE 6-1A IN FEMA PUBLICATION P-758 |
| | NEITHER THE LATERAL ADDITION NOR THE REMODEL IS |
| | REQUIRED TO COMPLY WITH NFIP REQUIREMENTS FOR NEW |
| | CONSTRUCTION. |