Plan Review Notes For Permit 13110333
Permit Number 13110333
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-27 16:57:28RETURNED TO BIN R21
  
2013-12-27 16:56:24AS PER FBC-R 314 & 315 SMOKE & CARBON MONOXIDE
 DETECTION IS REQUIRED. AS PER NFPA 72 SECTION 29.8.3.4
 THE SMOKE DETECTORS OUTSIDE THE MASTER BATHROOM DOOR
 SHALL BE EITHER ELIMINATED AS NON REQUIRED, OR
 RELOCATED AWAY FROM THE BATHROOM DOOR.