| Plan Review Notes For Permit 13110333 |
| Permit Number |
13110333 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-07 17:22:29 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR | | | FL#735.7 (NOA NO. 12-0716.18) ARE NOT SIGNED AND SEALED | | | AS REQUIRED BY FS481. THE CALCULATIONS DO NOT REFERENCE | | | THE PRODUCT APPROVAL NOA NUMBER, THE PAGE NUMBER OF THE | | | APPROVED ASSEMBLY OR THE FASTENING OPTION. PLEASE | | | CORRECT. | | | | | | 2) THE MECHANICAL PLANS SPECIFY LOUVERED DOORS ON THE | | | AIR HANDLER CLOSETS TO PROVIDE FOR THE RETURN AIR. THIS | | | IS NOT REFLECTED IN THE DOOR SCHEDULE IN THE DOOR | | | SCHEDULE ON SHEET A-8. PLEASE ADDRESS THIS ISSUE. CITY | | | AMENDMENTS 107.2.1 | | | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR ALL | | | OF THE EXTERIOR DOOR TYPES SPECIFIED ON THE PLANS. DCA | | | RULE 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|