Plan Review Notes
Plan Review Notes For Permit 13110333
Permit Number 13110333
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-07 17:22:292010 FBC
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR
 FL#735.7 (NOA NO. 12-0716.18) ARE NOT SIGNED AND SEALED
 AS REQUIRED BY FS481. THE CALCULATIONS DO NOT REFERENCE
 THE PRODUCT APPROVAL NOA NUMBER, THE PAGE NUMBER OF THE
 APPROVED ASSEMBLY OR THE FASTENING OPTION. PLEASE
 CORRECT.
  
 2) THE MECHANICAL PLANS SPECIFY LOUVERED DOORS ON THE
 AIR HANDLER CLOSETS TO PROVIDE FOR THE RETURN AIR. THIS
 IS NOT REFLECTED IN THE DOOR SCHEDULE IN THE DOOR
 SCHEDULE ON SHEET A-8. PLEASE ADDRESS THIS ISSUE. CITY
 AMENDMENTS 107.2.1
  
 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR ALL
 OF THE EXTERIOR DOOR TYPES SPECIFIED ON THE PLANS. DCA
 RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]