Plan Review Notes
Plan Review Notes For Permit 13110271
Permit Number 13110271
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-21 17:04:18BUILDING PLAN REVIEW
 PERMIT: 13110271
 ADD: 1750 OKEECHOBEE ROAD
 CONT: THORTON & THORTON INC.
 TEL: (321)507-4755
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 21/ 2013
 ACTION: DENIED
  
 1) THERE IS A DISCREPANCY BETWEEN THE LIFE SAFETY PLAN
 A2.0 AND E-2:
 1A) DOOR 26 REVERSE DOOR SWING
  
 1B) DOOR # 19 REVERSE SWING
  
 1C) L.S. SHEET A2.0 DOOR # 19 MISSING EXIT LIGHT
  
 1D) SHOW EXITING PLAN, IT APPEARS THAT DOOR # 20 WILL
 BE SWINGING THE WRONG WAY WITH A OCCUPANT LOAD OF
 GREATER THAN 50. FBC-B 1008.1.2.
  
 2) PRODUCT APPROVALS WERE SUBMITTED FOR STOREFRONT
 WINDOWS AND FOR DOORS, THE PLANS DO NOT INDICATE WHICH
 OF THESE ELEMENTS ARE GOING TO BE CHANGED OUT, THE
 PLANS ALSO DON'T PROVIDE THE WIND DESIGN CRITERIA AND
 PRESSURES.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2..1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) SHEET A6.0 GAURDRAIL SYSTEM PLEASE INDICATE WHERE
 THE 30 INCHES ABOVE GRADE STARTS, FOR THE REQUIRED
 GAURDRAIL PORTION OF THE SYSTEM. 1013.1, THE PLANS DO
 NOT INDICATE A HANDRAIL AGAINST THE WALL PER 1012.2.
 NOR IS THERE A HANDRAIL PORTRAYED IN THE GAURDRAIL
 SYSTEM.
  
 4) SHEET A6.0 INDICATES NEW ROOFTOP UNITS THERE ARE NO
 STRUCTURAL SHEETS DEPICTING HOW TO TREAT THE ROOF
 FRAMING, NEW HOLES CUT INTO THE ROOF, NOR HOW THE NEW
 A/C CURBS WILL BE ATTACHED TO THE ROOFING FRAMING
 SYSTEM OR THE ROOF TOP UNITS ATTACHED TO THE ROOF
 CURBS.
  
 7) THE PLANS DO NOT INDICATE THE ROOF HEIGHT, THIS MAY
 OR MAY NOT APPLY:
 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
  
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
  
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
  
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES (152 MM) DEEP.
  
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
  
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
  
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS (488.2 KG/M2) PER SQUARE FOOT.
  
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24 INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  