Plan Review Notes
Plan Review Notes For Permit 13110257
Permit Number 13110257
Review Stop M
Sequence Number 2
Notes
Date Text
2014-01-08 09:08:312010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE SCOPE OF MECHANICAL WORK IS NOT CLEAR. NO HVAC
 EQUIPMENT IS SHOWN ON THE EXISTING FLOOR PLAN AND FROM
 THE NOTES IT APPEARS THAT A NEW SYSTEM IS BEING
 INSTALLED. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 2) IF A NEW HVAC SYSTEM IS TO BE INSTALLED, SUBMIT TWO
 COPIES OF EQUIPMENT SIZING CALCULATIONS, TWO SETS
 MECHANICAL PLANS SHOWING THE DUCT SIZES AND LOCATIONS,
 GRILL SIZES LOCATIONS AND CFMS AT EACH OUTLET. SHOW
 COMPLIANCE WITH FBCR M1602.04 FOR BALANCED RETURN AIR.
 INCLUDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. FBCR M1401.3, FBCR M1601.1 AND CITY
 AMENDMENTS 107.3.5.3
  