2014-01-08 09:26:302008 NEC
  
 DENIED BY ELECTRIC
  
 1) SPECIFY THE SCOPE OF THE ELECTRICAL WORK ON THE
 PLANS. IF NEW CIRCUITS ARE TO BE ADDED TO SERVICE NEW
 MECHANICAL OR OTHER EQUIPMENT, SHOW THAT THE EXISTING
 SERVICE AND PANEL ARE CAPABLE OF HANDLING THE
 ADDITIONAL LOADS, SPECIFY THE SIZE OF THE EXISTING
 SERVICE AND PROVIDE A PANEL SCHEDULE. CITY AMENDMENTS
 107.2.1 AND 107.3.5.3
  
 2) SHOW THE LOCATIONS OF THE SMOKE ALARMS REQUIRED BY
 FBC R314.3.1 ON THE PLANS.
  