| Plan Review Notes For Permit 13110257 |
| Permit Number |
13110257 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-01-08 09:26:30 | 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) SPECIFY THE SCOPE OF THE ELECTRICAL WORK ON THE | | | PLANS. IF NEW CIRCUITS ARE TO BE ADDED TO SERVICE NEW | | | MECHANICAL OR OTHER EQUIPMENT, SHOW THAT THE EXISTING | | | SERVICE AND PANEL ARE CAPABLE OF HANDLING THE | | | ADDITIONAL LOADS, SPECIFY THE SIZE OF THE EXISTING | | | SERVICE AND PROVIDE A PANEL SCHEDULE. CITY AMENDMENTS | | | 107.2.1 AND 107.3.5.3 | | | | | | 2) SHOW THE LOCATIONS OF THE SMOKE ALARMS REQUIRED BY | | | FBC R314.3.1 ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|