Plan Review Notes
Plan Review Notes For Permit 13110257
Permit Number 13110257
Review Stop B
Sequence Number 2
Notes
Date Text
2014-01-08 09:41:182010 FBC
  
 DENIED BY BUILDING
  
 1) THE ARCHITECT THAT SEALED THE PLANS HAS HAD HIS
 LICENSE REVOKED AND CAN NO LONGER PERFORM DESIGN WORK.
 THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL HAND
 WRITTEN SIGNATURE OF THE ARCHITECT THAT IS SIGNING AND
 SEALING THE PLANS. FACIMILIES, COPIES OR SIGNATURE
 STAMPS ARE NOT ACCEPTABLE. FBC 61G1-16.003
  
 2) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE WINDOW
 OPENING AT THE REAR ROOM WILL BE ENCLOSED. CITY
 AMENDMENTS 107.2.1 AND FBC R301.1
  
 3) REVISE THE PLANS AND THE WINDOW SCHEDULE TO SHOW THE
 LOCATIONS AND SIZES OF THE HORIZONTAL SLIDING WINDOWS
 REFERENCED IN YOUR LETTER. CITY AMENDMENTS 107.2.1 AND
 FBC R310
  
 4) SPECIFY THE WIND DESIGN DATA ( 170 MPH VULT,
 EXPOSURE CATEGORY D) AND SPECIFY THE REQUIRED OPENING
 PRESSURES ON THE PLANS. FBCR 301.2.1
  
 5) PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER FOR THE
 JELD-WEN EXTERIOR DOOR THAT WAS SUBMITTED. DCA RULE
 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]