| 2013-12-11 07:54:58 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) BECAUSE THE PROPOSED BATHROOM DOES NOT HAVE ANY | | | WINDOWS, IT IS REQUIRED BY FBC R303.3 TO HAVE A | | | MECHANICAL VENTILATION SYSTEM INSTALLED IN ACCORDANCE | | | WITH FBCR M1507. | | | | | | 2) A MECHANICAL SUB-PERMIT IS REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|