| 2013-12-11 09:42:59 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) IN ADDITION TO THE REQUIRED LIGHTING OUTLET AND | | | EXHAUST FAN, PROVIDE AT LEAST ONE 20 AMP, GFCI | | | PROTECTED, TAMPER-RESISTANT RECEPTACLE WITHIN 3 FEET OF | | | THE OUTSIDE EDGE OF THE BASIN IN THE BATHROOM. NEC | | | 210.52(D) , 210.8, 406.11, 210.11(C)(3) | | | | | | 2) AN ELECTRICAL SUB-PERMIT IS REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|