Plan Review Notes
Plan Review Notes For Permit 13110257
Permit Number 13110257
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-11 06:52:482010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS THAT WERE SUBMITTED ARE TOO SMALL.
 BUILDING PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM
 1/8 INCH SCALE PER CITY AMENDMENTS 107.2.1.4
  
 2) PLANS SUBMITTED FOR PUBLIC RECORD FROM AN ARCHITECT
 ARE REQUIRED TO BE DATED, SIGNED AND SEALED BY HIM. THE
 ARCHITECT HAND WRITTEN SIGNATURE IS REQUIRED. COPIES,
 STAMPS OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 481
 AND FAC 61G1-16.003
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE ES
 FIXED WINDOWS ARE EXPIRED. SUBMIT TWO CURRENT COPIES OF
 THE PRODUCT APPROVALS AS REQUIRED BY DCA RULE 9N-3.
  
 4) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 THE EXTERIOR DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 5) PRODUCT APPROVALS WERE SUBMITTED FOR CASEMENT
 WINDOWS, HOWEVER, NONE WERE SPECIFIED IN THE WINDOW
 SCHEDULE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 6) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS USED TO CONNECT THE DOUBLE WINDOWS
 AS REQUIRED BY DCA RULE 9N-3.
  
 7) THE BEDROOM WINDOWS NEED TO COMPLY WITH FBC R310 FOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS AND THE REQUIRED
 NET CLEAR OPENING AREA, OPENING HEIGHT AND OPENING
 WIDTH. THIS MAY REQUIRE INSTALLING CASEMENT WINDOWS OR
 SINGLE HUNG COMPACT EGRESS WINDOWS THAT CAN SWING OPEN.
  
 8) THE SCOPE OF WORK ON THE APPLICATION SPECIFIES THE
 REPLACEMENT OF 17 WINDOWS AND 3 EXTERIOR DOORS. CLEARLY
 INDICATE THE SPECIFIC DOORS AND WINDOWS THAT ARE TO BE
 REPLACED ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]