2013-11-07 18:11:36CONDOMINIUM (R2) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- BUILDING CONTRACTOR CAN NOT PERFORM ANY STRUCTURAL
 WORK ON BUILDINGS THAT EXCEED THREE STORIES IN HEIGHT.
 SEC. 489.105(3)(B) OF FLORIDA STATUTE. NEED GC TO APPLY
 FOR THIS PERMIT AND REVISE THE NOTICE OF COMMENCEMENT
 ACCORDINGLY.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE GARAGE DOOR TO BE INSTALLED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) THE GARAGE DOOR PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 4- ENGINEER'S DRAWING IS MISSING THE FOLLOWING:
 A) ALL THE WIND DESIGN DATA REQUIRED BY SEC. 1603.1.4
 OF FBC-2010. (***NOTE: THIS BUILDING IS LOCATED IN
 EXPOSURE "D". SEE SEC. 1609.4.3 OF 2010 FBC).
  
 B) KEY PLAN SHOWING THE LOCATION/AREA OF WORK IN THE
 BUILDING. SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 C) ENGINEER TO PROVIDE HIS NAME, LICENSE NUMBER AND
 ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION
 NUMBER (O'DONNELL, NACCARATO, MIGNOGNA & JACKSON, INC.)
 AS REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  