Plan Review Notes
Plan Review Notes For Permit 13110240
Permit Number 13110240
Review Stop P
Sequence Number 1
Notes
Date Text
2013-12-12 17:05:43RESIDENTIAL (R3) ADDITION/ALTERATION, PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM:
 A) ONLY THE FIXTURES WITHIN THE "BATHROOM GROUPS" SHALL
 CONNECT TO THE WET VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 HORIZONTAL WET VENT. SEC. P3108.1 OF 2010
 FBC-RESIDENTIAL.
 BATHROOM GROUPS WET VENT IS NOT SHOWN CORRECTLY.
 SEPARATE THE BATHROOM GROUPS HORIZONTAL WET VENTS FROM
 THE MAIN DRAIN LINE.
  
 B) NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 CONNECTION. SEC. P3108.2.1 OF 2010 FBC-RESIDENTIAL. TUB
 AND TOILET FROM BATHROOM #2 ARE NOT PROPERLY VENTED.
  
 C) WASHER DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE
 BATHROOM GROUP HORIZONTAL WET VENT. SEC. P3108.1
  
 D) CLARIFY HOW ARE THE KITCHEN SINK AND LIVING ROOM BAR
 SINK VENTED. STUDOR VENT OR DRY VENT. RISER DIAGRAM
 SHOWS BOTH. HOW TO INSTALL DRY VENT ON KITCHEN ISLAND
 SINK?. SEC. 1072.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712