| Plan Review Notes For Permit 13110240 |
| Permit Number |
13110240 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-12 17:06:06 | RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS | | | REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- HVAC PLAN TO SHOW COMPLIANCE WITH THE BALANCED | | | RETURN AIR REQUIRED FOR THE HABITABLE ROOMS (OFFICE AND | | | ALL BEDROOMS). SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- HVAC PLAN TO SHOW THE SUPPLY AIR (CFM'S) FOR EACH | | | ROOM. SEC. M1601.1 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|