Plan Review Notes
Plan Review Notes For Permit 13110215
Permit Number 13110215
Review Stop B
Sequence Number 3
Notes
Date Text
2014-01-06 14:50:23APPROVED WITH EXCEPTIONS
  
 REVISIONS REQUIRED
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED STRUCTURAL
 DETAILS CLARIFYING THE INSTALLATION OF THE FRONT ENTRY
 DOOR ASSEMBLY WITH THE GLASS BLOCK SIDELITES AND
 TRANSOM.
  
 2) THE PRODUCT APPROVALS FOR THE LOW SLOPE ROOFING
 MATERIAL (FL# 9930 SINGLE PLY ROOF SYSTEM) THAT WAS
 SUBMITTED HAS NUMEROUS SYSTEMS WITH DIFFERENT MAXIMUM
 DESIGN PRESSURES AND LIMITATIONS FOR EACH DECK TYPE.
 THIS PROJECT HAS BOTH WOOD AND CONCRETE DECK TYPES.
 PLEASE SPECIFY THE SPECIFIC SYSTEM THAT WILL BE
 INSTALLED FOR EACH DECK TYPE AND THE MAXIMUM DESIGN
 PRESSURE FOR EACH. SUBMIT ALL ENHANCED FASTENING
 CALCULATIONS IF REQUIRED. THE REQUIRED UPLIFTS FOR ROOF
 ZONES 1, 2 AND 3 ARE -37.9 PSF, -63.6 PSF AND - 95.7
 PSF FOR THIS PROJECT.