| Plan Review Notes For Permit 13110215 |
| Permit Number |
13110215 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-01-06 14:50:23 | APPROVED WITH EXCEPTIONS | | | | | | REVISIONS REQUIRED | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED STRUCTURAL | | | DETAILS CLARIFYING THE INSTALLATION OF THE FRONT ENTRY | | | DOOR ASSEMBLY WITH THE GLASS BLOCK SIDELITES AND | | | TRANSOM. | | | | | | 2) THE PRODUCT APPROVALS FOR THE LOW SLOPE ROOFING | | | MATERIAL (FL# 9930 SINGLE PLY ROOF SYSTEM) THAT WAS | | | SUBMITTED HAS NUMEROUS SYSTEMS WITH DIFFERENT MAXIMUM | | | DESIGN PRESSURES AND LIMITATIONS FOR EACH DECK TYPE. | | | THIS PROJECT HAS BOTH WOOD AND CONCRETE DECK TYPES. | | | PLEASE SPECIFY THE SPECIFIC SYSTEM THAT WILL BE | | | INSTALLED FOR EACH DECK TYPE AND THE MAXIMUM DESIGN | | | PRESSURE FOR EACH. SUBMIT ALL ENHANCED FASTENING | | | CALCULATIONS IF REQUIRED. THE REQUIRED UPLIFTS FOR ROOF | | | ZONES 1, 2 AND 3 ARE -37.9 PSF, -63.6 PSF AND - 95.7 | | | PSF FOR THIS PROJECT. |
|