| 2014-01-06 10:59:58 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) PROVIDE A STRUCTURAL DETAIL OF THE ENTRY DOOR | | | ASSEMBLY SHOWN WITH GLASS BLOCK SIDELITES AND TRANSOM. | | | PROVIDE ALL DETAILS AS TO HOW THIS ASSEMBLY IS TO BE | | | INSTALLED. CITY AMENDMENTS 107.2.1.3 | | | | | | 2) THE PRODUCT APPROVALS SUBMITTED FOR THE GLASS BLOCK | | | AT THE ENTRY DOOR HAS A SMALL MISSILE IMPACT RATING AND | | | WILL REQUIRE IMPACT PROTECTION. SUBMIT PRODUCT | | | APPROVALS FOR STORM PANELS OR PRODUCT APPROVALS FOR | | | LARGE MISSILE IMPACT RATED GLASS BLOCK. DCA RULE 9N-3 | | | | | | 3) THE PRODUCT APPROVALS FOR THE LOW SLOPE ROOFING | | | MATERIAL (FL# 9930 SINGLE PLY ROOF SYSTEM) THAT WAS | | | SUBMITTED HAS NUMEROUS SYSTEMS WITH DIFFERENT MAXIMUM | | | DESIGN PRESSURES AND LIMITATIONS FOR EACH DECK TYPE. | | | THIS PROJECT HAS BOTH WOOD AND CONCRETE DECK TYPES. | | | PLEASE SPECIFY THE SPECIFIC SYSTEM THAT WILL BE | | | INSTALLED FOR EACH DECK TYPE AND THE MAXIMUM DESIGN | | | PRESSURE FOR EACH. SUBMIT ALL ENHANCED FASTENING | | | CALCULATIONS IF REQUIRED. THE REQUIRED UPLIFTS FOR ROOF | | | ZONES 1, 2 AND 3 ARE -37.9 PSF, -63.6 PSF AND - 95.7 | | | PSF FOR THIS PROJECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|