Plan Review Notes
Plan Review Notes For Permit 13110215
Permit Number 13110215
Review Stop M
Sequence Number 1
Notes
Date Text
2013-12-09 17:59:462010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 2) THE TRANSFER DUCTS FOR BEDROOM NUMBER 2 AND THE
 MASTER BEDROOM ARE TOO SMALL. FBCR M1602.4 REQUIRES THE
 TRANSFER DUCTS TO BE 1.5 TIMES THE SUPPLY DUCTS
 ENTERING THE ROOM OR MASTER SUITE AND THE DOOR HAVING
 AN UNRESTRICTED 1" UNDERCUT. THE TRANSFER DUCT FOR
 BEDROOM #2 SHOULD BE 9" AND THE ONE AT THE MASTER SUITE
 SHOULD BE 14". PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]