| Plan Review Notes For Permit 13110215 |
| Permit Number |
13110215 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-09 17:59:46 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 2) THE TRANSFER DUCTS FOR BEDROOM NUMBER 2 AND THE | | | MASTER BEDROOM ARE TOO SMALL. FBCR M1602.4 REQUIRES THE | | | TRANSFER DUCTS TO BE 1.5 TIMES THE SUPPLY DUCTS | | | ENTERING THE ROOM OR MASTER SUITE AND THE DOOR HAVING | | | AN UNRESTRICTED 1" UNDERCUT. THE TRANSFER DUCT FOR | | | BEDROOM #2 SHOULD BE 9" AND THE ONE AT THE MASTER SUITE | | | SHOULD BE 14". PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|