| Date |
Text |
| 2013-12-10 06:44:10 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN EXPOSURE C PER FBC |
| | R301.1.4.3. PLEASE REVISE PLANS. |
| | |
| | 2) THE WIND VELOCITY PRESSURES FOR WALL ZONES 4 & 5 ON |
| | SHEET S-4 ARE HIGHER THAN REQUIRED FOR A STRUCTURE |
| | LOCATED IN EXPOSURE B OR C WITH A MEAN ROOF HEIGHT OF |
| | LESS THAN 15 FEET AND A WINDSPEED OF 132 MPH VASD. SEE |
| | FBCR 301.2.1 AND R301.2.1.3 |
| | |
| | 3) SPECIFY THE WIND VELOCITY PRESSURES FOR THE LOW |
| | SLOPE ROOF ZONES 1, 2, AND 3 ON THE PLANS. |
| | |
| | 4) TRUSS NOTE (G) ON SHEET S-4 INCORRECTLY SPECIFIES A |
| | 140 MPH 3 SECOND GUST AND 120 MPH SUSTAINED WINDSPEED |
| | AND EXPOSURE B FOR THIS PROJECT. |
| | |
| | 5) PROVIDE A SURFACE WATER DRAINAGE PLAN THAT SHOWS |
| | COMPLIANCE WITH FBCR 401.3. |
| | |
| | 6) SHOW COMPLIANCE WITH FBCR 806.2 FOR REQUIRED TOTAL |
| | NET FREE VENTILATING AREA OF THE ENCLOSED ATTIC SPACE. |
| | INDICATE ON THE PLANS THE SIZE AND LOCATIONS OF THE |
| | ATTIC VENTS ON THE PLANS WITH CALCULATIONS. |
| | |
| | 7) THE MINIMUM THICKNESS FOR STUCCO ON A VERTICAL WALL |
| | ON METAL LATH OVER A SOLID BASE IS 7/8 " PER FBCR 703.6 |
| | AND ASTM C 926. PLEASE REVISE THE PARAPET WALL SECTIONS |
| | ON A-6. |
| | |
| | 8) FBC 703.6.3 REQUIRES A BOND BREAK BETWEEN THE STUCCO |
| | AND THE WATER-RESISTIVE BARRIER. PLEASE REVISE THE |
| | PARAPET WALL SECTIONS ON A-6. |
| | |
| | 9) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS, WINDOWS, STRUCTURAL MULLIONS, GLASS |
| | BLOCK, ROOFING MATERIAL AND STRUCTURAL CONNECTORS THAT |
| | WILL BE USED ON THIS PROJECT AS REQUIRED BY DCA RULE |
| | 9N-3. |
| | |
| | 10) CITY AMENDMENT 107.3.4.1 REQUIRES THE PRODUCT |
| | APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD FOR THE PROJECT. |
| | |
| | 11) THE VALUE FOR THIS PROJECT HAS BEEN INCREASED FROM |
| | $150,000.00 TO $197,000.00 BASED ON LATEST ICC |
| | VALUATION DATA. CITY AMENDMENTS 109.3 |
| | |
| | NOTE: IN ORDER TO SPEED THE REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | ITEMS WAS ADDRESSED. |
| | |