| Plan Review Notes For Permit 13110190 |
| Permit Number |
13110190 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-11-13 15:55:26 | BUILDING PROVISO | | | | | | SUBMIT TWO SETS OF AS BUILT REVISIONS CORRECTING THE | | | FOLLOWING DEFICIENCIES. | | | | | | 1) THE REVISED PLANS SPECIFY THAT ALL NEW INTERIOR | | | WALLS WILL BE 2 - 1/2" METAL STUD WALL WITH 3 - 1/2" | | | INSULATION IN STUD SPACE. INSULATION IS TOO THICK FOR | | | THE WALL. | | | | | | 2) THE REVISED PLANS SPECIFY NEW 3 -1/2" WALLS (2 - | | | 1/2" STUD WITH 1/2" DRYWALL EA. SIDE) EXTENDING FROM 4 | | | - 1/2" WALLS. PLEASE CLARIFY. | | | | | | 2) CHANGING THE SWING ON THE DOOR TO OFFICE 2, AS SHOWN | | | ON THE REVISION, DOES NOT CORRECT THE ACCESSIBILITY | | | ISSUE. THE DOOR HAS TO BE EVALUATED FOR BOTH ENTERING | | | AND LEAVING THE ROOM. A FRONT APPROACH ON THE PULL SIDE | | | OF THE DOOR REQUIRES A MINIMUM 18" WALL SPACE TO THE | | | LATCH SIDE OF THE DOOR. FBC ACCESSIBILITY 404.2.4.1 | | | NOTE: A RIGHT HAND INSWING DOOR WOULD BE COMPLIANT. | | | | | | |
|