Plan Review Notes For Permit 13110189
Permit Number 13110189
Review Stop P
Sequence Number 1
Notes
Date Text
2013-11-12 17:45:172010 FBC
  
 DENIED BY PLUMBING
  
 1) `THE SCOPE OF WORK FOR THIS PROJECT REQUIRES A
 BUILDING CONTRACTOR TO PULL A RESIDENTIAL REMODEL
 PERMIT. THIS PLUMBING PERMIT SHOULD BE TIED TO THE
 REMODEL PERMIT AND CAN NOT BE ISSUED UNTIL A REMODEL
 PERMIT IS ISSUED. PERMITS FOR ELECTRIC WILL ALSO BE
 REQUIRED. A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR THE GAS PERMIT.
  
 2) SUBMIT TWO SETS OF DIMENSIONED PLANS FOR THE NEW
 BATHROOM TO SHOW COMPLIANCE WITH FBC R307.1. THE
 ADDRESS OF THE PROJECT, THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO
 BE ON THE PLANS.
  
 3) SUBMIT TWO SETS OF A FLOOR PLAN OF THE EXISTING
 DWELLING SPECIFYING THE EXISTING ROOMS AND SHOWING THE
 LOCATION OF THE PROPOSED BATHROOM AND NEW TANKLESS
 WATER HEATER. CITY AMENDMENTS 107.2.1. THE ADDRESS OF
 THE PROJECT, THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON
 THE PLANS.
  
 4) SUBMIT TWO SETS OF A RISER DIAGRAM FOR THE NEW
 BATHROOM. SPECIFY THE PIPING MATERIAL, PIPE SIZES AND
 LOCATIONS FOR THE WASTE AND VENT PIPING. THE ADDRESS OF
 THE PROJECT, THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON
 THE PLANS. CITY AMENDMENTS 107.3.5
  