| 2013-11-22 10:24:40 | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | |
| | 1. THE COMMON AREA TOILET FACILITIES ARE OVER 500' FROM |
| | THE STORE ENTRANCE. PLEASE VERIFY THE PUBLIC ACCESS |
| | DISTANCE WITH THE PALM BEACH OUTLET MALL. ALSO THE |
| | ROUTE TO THE STORE FACILITIES APPEARS TO BE THROUGH A |
| | STORAGE (STOCK) AREA. SHEET A0.01 LISTS THE NON SALES |
| | AREA AS A STOCKROOM. THE RESTROOMS WILL BE REQUIRED TO |
| | BE OPEN TO PUBLIC ACCESS. |
| | |
| | 403.3.2 LOCATION OF TOILET FACILITIES IN OCCUPANCIES |
| | OTHER THAN COVERED MALLS. |
| | IN OCCUPANCIES OTHER THAN COVERED MALL BUILDINGS, THE |
| | REQUIRED PUBLIC AND EMPLOYEE TOILET FACILITIES SHALL BE |
| | LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE |
| | SPACE REQUIRED TO BE PROVIDED WITH TOILET FACILITIES, |
| | AND THE PATH OF TRAVEL TO SUCH FACILITIES SHALL NOT |
| | EXCEED A DISTANCE OF 500 FEET (152 M). |
| | |
| | 403.3.1 ACCESS. |
| | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY |
| | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES |
| | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR |
| | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE |
| | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO |
| | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE |
| | BUILDING IS OCCUPIED. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |