| Plan Review Notes For Permit 13110136 |
| Permit Number |
13110136 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-12 14:44:47 | THE FOLLOWING ELECTRICAL CORRECTIONS SHALL BE MADE TO | | | THE SUBMITTED PLANS FOR A SUCCESSFUL ELECTRICAL REVIEW: | | | 1. THE PANEL SCHEDULE AS SHOWN ON THE PLANS, DOES NOT | | | MATCH THE RISER DIAGRAM OR THE ELECTRICAL LAYOUT AS | | | SHOWN ON THE FLOOR PLAN. YOU ARE INDICATING TWO | | | DIFFERENT METHODS TO SUPPLY ELECTRIC POWER TO THE SHED. | | | WHICHEVER METHOD YOU DECIDE TO USE, ALL THE DRAWINGS | | | HAVE TO COINCIDE. | | | 2. REMOVE OR CORRECT THE ELECTRICAL NOTE ON THE | | | SUBMITTED PLANS, AS A NEW METER IS BEYOND THE SCOPE OF | | | THIS PERMIT. |
|