Plan Review Notes
Plan Review Notes For Permit 13110043
Permit Number 13110043
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-04 14:44:52RESIDENTIAL (R3) ROOF REPAIRS, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 STATES "REPAIR FLAT ROOF". INFORMATION SUBMITTED ARE
 COPIES OF OLD PERMIT 04060371, WHICH DOESN'T INCLUDE
 ANY FLAT ROOF. PRODUCT APPROVAL SUBMITTED IFS FOR
 SHINGLES NOT FLAT ROOF. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 2- SPECIFY HOW MUCH AREA OF FLAT ROOF IS GOING TO BE
 REPAIRED. IF FLAT ROOF AREA EXCEEDS 25% OF THE FLAT
 ROOF AREA, THEN NEED TO RE-ROOF ENTIRE FLAT ROOF AREA.
 SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING. AREA TO BE
 REPAIRED WILL BE VERIFIED BY BUILDING INSPECTOR.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE FLAT ROOF PRODUCT APPROVAL TO BE
 USED. AND:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE RAS 117 CALCULATIONS FOR THE NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES THE RAS
 117 CALCULATIONS TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FESS. WILL BE ADJUSTED ONCE TOTAL ROOF
 SQUARE AREA IS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATIONS PLANS EXAMINER
 (561) 805-6712
  