| 2013-11-04 14:44:52 | RESIDENTIAL (R3) ROOF REPAIRS, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION |
| | STATES "REPAIR FLAT ROOF". INFORMATION SUBMITTED ARE |
| | COPIES OF OLD PERMIT 04060371, WHICH DOESN'T INCLUDE |
| | ANY FLAT ROOF. PRODUCT APPROVAL SUBMITTED IFS FOR |
| | SHINGLES NOT FLAT ROOF. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 2- SPECIFY HOW MUCH AREA OF FLAT ROOF IS GOING TO BE |
| | REPAIRED. IF FLAT ROOF AREA EXCEEDS 25% OF THE FLAT |
| | ROOF AREA, THEN NEED TO RE-ROOF ENTIRE FLAT ROOF AREA. |
| | SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING. AREA TO BE |
| | REPAIRED WILL BE VERIFIED BY BUILDING INSPECTOR. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE FLAT ROOF PRODUCT APPROVAL TO BE |
| | USED. AND: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE RAS 117 CALCULATIONS FOR THE NAIL ENHANCING |
| | AT PERIMETER AND CORNER AREAS AS REQUIRED TO MEET THE |
| | DESIGN PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES THE RAS |
| | 117 CALCULATIONS TO BE SIGNED AND SEALED, THEN PROVIDE |
| | SIGNED AND SEALED CALCULATIONS. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE |
| | ALL LABOR, MATERIALS, OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FESS. WILL BE ADJUSTED ONCE TOTAL ROOF |
| | SQUARE AREA IS PROVIDED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATIONS PLANS EXAMINER |
| | (561) 805-6712 |
| | |