| Plan Review Notes For Permit 13110011 |
| Permit Number |
13110011 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-02 11:03:50 | THE FOLLOWING ITEMS NEED TO BE ADDRESSED: | | | 1. CONTROL WIRE INSULATION AS PER NEC 620.11(B) | | | 2. INDICATE CONDUCTOR INSULATION AS INDICATED IN NEC | | | 620.36 AS WELL AS RACEWAY TYPE FROM PANEL "1XA" TO | | | PANEL "PBX" | | | 3. SHOW THE PROPOSED FANS ON THE RISER DIAGRAM. | | | 4. INDICATE PROPER GROUNDING AS PER NEC 620.82 OR 83 | | | 5. PROVIDE ELECTRICAL DETAILS FOR "ESF1" & "ESF2" | | | 6. INDICATE ALL RACEWAY TYPES AND CONDUCTOR INSULATION | | | ON DRAWINGS |
|