Plan Review Notes
Plan Review Notes For Permit 13101150
Permit Number 13101150
Review Stop M
Sequence Number 4
Notes
Date Text
2014-02-03 16:27:18 
 SEE COMMENTS FROM THIRD REVIEW BELOW:
  
  
  
  
 THIRD MECHANICAL REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW A/C PLAN SUBMITTED.
 A) ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL.
 REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS
 REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT
 APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4"
 CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE
 LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF
 THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR
 EXACT LOCATION AND REVISE DETAIL AS REQUIRED.
  
  
  
 B) ***ORIGINAL COMMENT: AHU #1 IS MISSING THE BALANCED
 RETURN AIR REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN LAYOUT FOR
 LOT 48. THEREFORE, UNABLE TO VERIFY COMPLIANCE.
  
  
 C) ***ORIGINAL COMMENT: REVISE SIZE OF TRANSFER DUCT
 SHOWN FOR MASTER BEDROOM. 14" TRANSFER DUCT DOESN'T
 COMPLY WITH EXCEPTION #1 AND #3 OF SEC. M1602.4.
  
 ***RESPONSE:
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN LAYOUT FOR
 LOT 48. THEREFORE, UNABLE TO VERIFY COMPLIANCE.
 NOTE: KEEP IN MIND THAT ALL SUPPLY AIR INTO THE MASTER
 SUITE SHALL BE INCLUDED (INCLUDE SUPPLY TO BATHROOM,
 CLOSETS, ETC).
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved