2013-12-31 16:19:51NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE
 USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS.
 NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC.
 403.61 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT
 COMMENT).
  
 2- NEW A/C PLAN SUBMITTED. A) REVISE THE CU MOUNTING
 DETAIL. REVISE THE NUMBER AND LOCATION OF HURRICANE
 CLIPS AS REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA
 PRODUCT APPROVAL FL14239 SPECIFIED ON THE DETAIL.
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2010 AND SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 B) AHU #1 IS MISSING THE BALANCED RETURN AIR REQUIRED
 BY SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 C) REVISE SIZE OF TRANSFER DUCT SHOWN FOR MASTER
 BEDROOM. 14" TRANSFER DUCT DOESN'T COMPLY WITH
 EXCEPTION #1 AND #3 OF SEC. M1602.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712