Date Text
2013-11-22 16:33:3711/22/13 TALKED TO MS. TERRY. THEY WILL ADDRESS PROVISO
 ITEMS BEFORE PERMIT ISSUANCE. JG.
2013-11-21 18:02:28 
  
  
  
  
 MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE
 USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS.
 NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC.
 403.61 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- ALL THE EQUIPMENT SHOWN ON THE A/C PLANS NEED TO
 MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING
 CALCULATIONS.
  
 3- A/C PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY
 AMENDMENTS.