| Plan Review Notes For Permit 13101150 |
| Permit Number |
13101150 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-22 16:33:37 | 11/22/13 TALKED TO MS. TERRY. THEY WILL ADDRESS PROVISO | | | ITEMS BEFORE PERMIT ISSUANCE. JG. | | 2013-11-21 18:02:28 | | | | | | | | | | | | | | | | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE | | | USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS. | | | NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC. | | | 403.61 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- ALL THE EQUIPMENT SHOWN ON THE A/C PLANS NEED TO | | | MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING | | | CALCULATIONS. | | | | | | 3- A/C PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY | | | AMENDMENTS. |
|