| Plan Review Notes For Permit 13101148 |
| Permit Number |
13101148 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2014-02-03 16:10:55 | CHECKLIST: | | | | | | 1- ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS | | | SUBMITTED ARE FOR MODEL 2566. ACCORDING TO PLANS | | | SUBMITTED LOT 93 IS FOR MODEL 2500. REVISE AS REQUIRED | | | TO MATCH. | | | | | | 2- SEE COMMENTS BELOW FROM THIRD REVIEW: | | | | | | | | | THIRD MECHANICAL REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- NEW A/C PLAN SUBMITTED. | | | ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL. | | | REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS | | | REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT | | | APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO | | | MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC. | | | M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | ***RESPONSE: | | | INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4" | | | CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE | | | LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF | | | THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR | | | EXACT LOCATION AND REVISE DETAIL AS REQUIRED. | | | | | | | | | 2- NEW COMMENT. | | | A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS | | | BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|