Plan Review Notes
Plan Review Notes For Permit 13101148
Permit Number 13101148
Review Stop M
Sequence Number 4
Notes
Date Text
2014-02-03 16:10:55CHECKLIST:
  
 1- ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS
 SUBMITTED ARE FOR MODEL 2566. ACCORDING TO PLANS
 SUBMITTED LOT 93 IS FOR MODEL 2500. REVISE AS REQUIRED
 TO MATCH.
  
 2- SEE COMMENTS BELOW FROM THIRD REVIEW:
  
  
 THIRD MECHANICAL REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW A/C PLAN SUBMITTED.
 ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL.
 REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS
 REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT
 APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4"
 CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE
 LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF
 THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR
 EXACT LOCATION AND REVISE DETAIL AS REQUIRED.
  
  
 2- NEW COMMENT.
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS
 BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  