Plan Review Notes
Plan Review Notes For Permit 13101148
Permit Number 13101148
Review Stop M
Sequence Number 3
Notes
Date Text
2014-01-24 13:39:16THIRD MECHANICAL REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ***ORIGINAL COMMENT:
 REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE
 USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS.
 NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC.
 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT CALCULATIONS WERE
 DONE FOR ALL POSSIBLE BUILDING ORIENTATIONS AT THE END
 OF THE REPORT. CALCULATIONS AND LISTED EQUIPMENT STILL
 SHOW FRONT DOOR FACING NORTHEAST, WHICH IS NOT THE
 CORRECT BUILDING ORIENTATION FOR THIS BUILDING.
 CALCULATIONS AND EQUIPMENT LISTED NEED TO SHOW SPECIFIC
 BUILDING ORIENTATION AS REQUIRED BY SEC. 403.6.1.
 IN ADDITION, CALCULATIONS SHOWING THE ROTATIONS AT THE
 END OF THE REPORT DON'T MATCH THOSE CALCULATIONS SHOWN
 AT THE BEGINNING OF THE REPORT.
  
  
  
 2- NEW A/C PLAN SUBMITTED.
 ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL.
 REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS
 REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT
 APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4"
 CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE
 LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF
 THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR
 EXACT LOCATION AND REVISE DETAIL AS REQUIRED.
  
  
 3- NEW COMMENT.
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS
 BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved