| 2014-01-24 13:39:16 | THIRD MECHANICAL REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- ***ORIGINAL COMMENT: |
| | REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE |
| | USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS. |
| | NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC. |
| | 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | ***RESPONSE: |
| | INFORMATION SUBMITTED STATED THAT CALCULATIONS WERE |
| | DONE FOR ALL POSSIBLE BUILDING ORIENTATIONS AT THE END |
| | OF THE REPORT. CALCULATIONS AND LISTED EQUIPMENT STILL |
| | SHOW FRONT DOOR FACING NORTHEAST, WHICH IS NOT THE |
| | CORRECT BUILDING ORIENTATION FOR THIS BUILDING. |
| | CALCULATIONS AND EQUIPMENT LISTED NEED TO SHOW SPECIFIC |
| | BUILDING ORIENTATION AS REQUIRED BY SEC. 403.6.1. |
| | IN ADDITION, CALCULATIONS SHOWING THE ROTATIONS AT THE |
| | END OF THE REPORT DON'T MATCH THOSE CALCULATIONS SHOWN |
| | AT THE BEGINNING OF THE REPORT. |
| | |
| | |
| | |
| | 2- NEW A/C PLAN SUBMITTED. |
| | ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL. |
| | REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS |
| | REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT |
| | APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO |
| | MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC. |
| | M1307.2.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | ***RESPONSE: |
| | INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4" |
| | CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE |
| | LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF |
| | THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR |
| | EXACT LOCATION AND REVISE DETAIL AS REQUIRED. |
| | |
| | |
| | 3- NEW COMMENT. |
| | A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS |
| | BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |