| 2013-12-31 13:56:37 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE | | | ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE | | | PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE | | | DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS | | | REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY | | | CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS | | | USING THE "ACTUAL" BUILDING ORIENTATION. (REPEAT | | | COMMENT). | | | | | | 2- NEW A/C PLAN SUBMITTED. A) REVISE THE CU MOUNTING | | | DETAIL. REVISE THE NUMBER AND LOCATION OF HURRICANE | | | CLIPS AS REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA | | | PRODUCT APPROVAL FL14239 SPECIFIED ON THE DETAIL. | | | REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF | | | 2010 AND SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE NAME | | | AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|