Plan Review Notes
Plan Review Notes For Permit 13101148
Permit Number 13101148
Review Stop M
Sequence Number 2
Notes
Date Text
2013-12-31 13:56:37NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE
 ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE
 PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE
 DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS
 USING THE "ACTUAL" BUILDING ORIENTATION. (REPEAT
 COMMENT).
  
 2- NEW A/C PLAN SUBMITTED. A) REVISE THE CU MOUNTING
 DETAIL. REVISE THE NUMBER AND LOCATION OF HURRICANE
 CLIPS AS REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA
 PRODUCT APPROVAL FL14239 SPECIFIED ON THE DETAIL.
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2010 AND SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 3- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE NAME
 AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712