2013-12-03 13:35:39NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE
 ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE
 PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE
 DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS
 USING THE "ACTUAL" BUILDING ORIENTATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712