| Plan Review Notes For Permit 13101138 |
| Permit Number |
13101138 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-04 18:58:30 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) SUBMIT TWO SETS OF LOAD CALCULATIONS FOR THE | | | DWELLING UNIT INCLUDING ALL OF THE NEW ELECTRICAL | | | EQUIPMENT. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE FOR THE | | | EXISTING SERVICE INCLUDING ALL NEW AND UPGRADED | | | CIRCUITS. CITY AMENDMENTS 107.3.5.3 | | | | | | 3) SUBMIT THE SPECIFICATIONS WITH THE ELECTRICAL | | | REQUIREMENTS FOR THE NEW TANKLESS ELECTRIC WATER | | | HEATER. NEC 110.3(B) | | | | | | 4) THE SMOKE ALARMS ARE TO BE LOCATED IN THE SLEEPING | | | ROOMS SO THAT THEY WILL PROVIDE THE MOST EFFECTIVE | | | COVERAGE IN ACCORDANCE WITH THEIR LISTING/LABELING. NEC | | | 110.3(B) | | | | | | 5) THE NAME AND LICENSE NUMBER OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | | ELECTRICAL DRAWINGS. FS 471.003(2)(H) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|