| Plan Review Notes For Permit 13101138 |
| Permit Number |
13101138 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-04 18:05:49 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) FOR RE-ROOFING OF THE UTILITY ROOM. SPECIFY THE | | | FASTENING OPTION LISTED ON PAGE 17 OF NOA NO. | | | 07-1219.09 THAT WILL BE USED TO INSTALL THIS SYSTEM. | | | SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR ENHANCED | | | FASTENING AT THE PERIMETER AND CORNER AREAS AS REQUIRED | | | BY LIMITATION #7 ON PAGE 19 OF THE PRODUCT APPROVAL. | | | | | | 2) BASED ON THE CONTRACT THAT WAS SUBMITTED THE PERMIT | | | VALUE FOR THE WORK WAS INCREASED FROM $ 25,900.00 TO $ | | | 53,500.00. CITY AMENDMENTS 109.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|