 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS:
  
 INDICATE THE PERCENTAGE OF THE BUILDING INVOLVED IN THE
 REHABILITATION. PER NFPA 101 SECTION 43.6.4.1, IN A
 BUILDING WITH REHABILITATION WORK AREAS INVOLVING OVER
 50 PERCENT OF THE AGGREGATE BUILDING AREA, AUTOMATIC
 SPRINKLER SYSTEMS SHALL BE PROVIDED ON THE HIGHEST
 FLOOR CONTAINING A REHABILITATION WORK AREA AND ON ALL
 FLOORS BELOW IN ACCORDANCE WITH THE REQUIREMENTS OF
 OTHER SECTIONS OF THIS CODE APPLICABLE TO NEW
 CONSTRUCTION FOR THE OCCUPANCY.
  
 PER SECTION7.2.2.6.4 (NFPA 101) ALL OPENINGS ADJACENT
 TO AND BELOW AN OUTSIDE STAIR SHALL BE PROTECTED WITH
 AN ASSEMBLY HAVING A MINIMUM 45-MINUTE FIRE PROTECTION
 RATING.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  