Plan Review Notes
Plan Review Notes For Permit 13101110
Permit Number 13101110
Review Stop B
Sequence Number 2
Notes
Date Text
2013-12-19 07:54:34BUILDING PLAN REVIEW
 PERMIT: 13101110
 ADD: 415 9TH ST
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURSDAY DEC 19/2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) 2ND REQUEST. 703.4 INTERIOR FINISH. THE INTERIOR
 FINISH OF WALLS AND CEILINGS IN EXITS AND CORRIDORS IN
 ANY WORK AREA SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. SEE 2010 FBC-B TABLE
 803.9.
 EXCEPTION: EXISTING INTERIOR FINISH MATERIALS THAT DO
 NOT COMPLY WITH THE INTERIOR FINISH REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. SHALL BE PERMITTED TO
 BE TREATED WITH AN APPROVED FIRE-RETARDANT COATING IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS TO
 ACHIEVE THE REQUIRED RATING.
  
 4) 705.2 GENERAL. THE MEANS OF EGRESS SHALL COMPLY WITH
 THE REQUIREMENTS OF THIS SECTION. EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF EGRESS SERVING
 IT COMPLIES WITH THE FLORIDA FIRE PREVENTION CODE.
 2. MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA
 FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.
  
 NOTE BOTH SHEET 1 & 2 INDICATE WINDOWS AND OR DOORS ON
 THE 1ST & 2ND FLOOR WITHIN 10 FEET OF THE EXTERIOR
 STAIR, PLEASE SHOW COMPLIANCE WITH THE 2010 FBC-B
 1026.6 EXTERIOR STAIRWAY PROTECTION. NOTE THE PROPOSED
 FIBERGLASS DOOR WILL NEED TO PROVIDE THE 1 HOUR FIRE
 RATING REQUIRED BY 1026.6.
  
 NO PRODUCT APPROVALS WERE SUBMITTED FOR THE INSTALATION
 OF 1 HR FIRE RATED GLASS BLOCK, DOES IT REQUIRE A METAL
 FRAME.
  
 THE PRODUCT APPROVALS SUBMITTED FOR EXTERIOR DOORS WAS
 A DUNBARTON REDIFLEX TWO PIECE STEEL FRAME AND TRINITY
 OPAQUE FIBERGLASS DOOR, THE PRODUCT APPROVAL DOES NOT
 INDICATE TESTING FOR 1 HOUR FIRE RATING OF DOOR.
  
 5-7) COMPLIED.
  
 NEW COMMENT:
  
 8) THE PRODUCT TESTING REPORT SUBMITTED FOR THE PRMIUM
 ATLANTIC ALUMINUM SINGLE HUNG WINDOW IS NEITHER A
 FLORIDA APPROVAL OR MIAMI-DADE NOA, IF SO PLEASE
 PROVIDE THE COVERSHEETS SHOWING IT IS REVIEWED UNDER
 THERE PROGRAMS.
  
 THE PLANS DO NOT INDICATE IF THE EXISTING WINDOW FRAMES
 ARE THE OLD DOUBLE SASH WOOD FRAMES WITH COUNTER WEIGHT
 POCKETS? THE REPORT SUBMITTED INDICATES THEY ARE FOR
 THRU JAMB INSTALATION, DOES THIS MEAN THE OLD EXISTING
 WINDOW FRAMES ARE LEFT INPLACE AND THESE ARE FIT
 DIRECTLY INTO THE EXISTING WINDOW FRAMES, IF SO HOW ARE
 THEY BEING FASTENED THRU TO THE FRAMING WALL MEMBERS?
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) SHEET A2 INDICATES THIS BUILDING IS A R-3
 OCCUPANCY, R-3 OCCUPANCY IS A ONE AND TWO FAMILY
 OCCUPANCY NOT FOUR UNITS. PLEASE CORRECT. SEE 2010
 FBC-B 310.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  