| 2013-11-22 10:27:48 | 415 9TH STREET | | | PERMIT #13101110 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | INDICATE THE PERCENTAGE OF THE BUILDING INVOLVED IN THE | | | REHABILITATION. PER NFPA 101 SECTION 43.6.4.1, IN A | | | BUILDING WITH REHABILITATION WORK AREAS INVOLVING OVER | | | 50 PERCENT OF THE AGGREGATE BUILDING AREA, AUTOMATIC | | | SPRINKLER SYSTEMS SHALL BE PROVIDED ON THE HIGHEST | | | FLOOR CONTAINING A REHABILITATION WORK AREA AND ON ALL | | | FLOORS BELOW IN ACCORDANCE WITH THE REQUIREMENTS OF | | | OTHER SECTIONS OF THIS CODE APPLICABLE TO NEW | | | CONSTRUCTION FOR THE OCCUPANCY. PER SECTION7.2.2.6.4 | | | (NFPA 101) ALL OPENINGS ADJACENT TO AND BELOW AN | | | OUTSIDE STAIR SHALL BE PROTECTED WITH AN ASSEMBLY | | | HAVING A MINIMUM 45-MINUTE FIRE PROTECTION RATING. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|