Plan Review Notes
Plan Review Notes For Permit 13101110
Permit Number 13101110
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-03 09:18:34ON THE FIRST REVIEW OF THE PLANS, THE FOLLOWING
 DEFICIENCIES WERE NOTED:
 1. RELOCATE THE SMOKE DETECTORS AWAY FROM THE CENTER OF
 THE ROOM IN ANTICIPATION OF CEILING FANS.
 2.SHOW SEPARATION BETWEEN UNIT 1 AND THE BASEMENT.
 3. THERE IS AN A/C UNIT INSIDE THE BATHROOM OF UNIT 3.
 4. AS PER FBC-R 303.8,MINIMUM HEATING IS REQUIRED; NO
 MENTION OF WHICH IS ADDRESSED. IF THE WINDOW A/C UNITS
 ARE REVERSIBLE, PLEASE STATE SO AND CORRECT THE
 INDIVIDUAL LOAD CALC ACCORDINGLY.
 5. AS PER NEC 210.52(F), A LAUNDRY CIRCUIT SHALL BE
 PROVIDED IN EACH UNIT UNLESS COMMON LAUNDRY FACILITIES
 ARE ON PREMISES. AGAIN, CORRECT THE DRAWINGS AND THE
 LOAD CALCS AND PANEL SCHEDULES ACCORDINGLY. IF COMMON
 LAUNDRY FACILITIES ARE BEING IMPLEMENTED, ADDRESS SO
 AND MAKE THE NECESSARY CHANGE TO THE HOUSE PANEL AND
 LOAD CALCS.
 6. FOR LIFE SAFETY, MINIMUM LIGHTING SHALL BE PROVIDED
 IN THE ATTIC.
 7. DUE TO THE MISSING LOADS, PROPER LOAD CALCS ARE
 IMPOSSIBLE. PROVIDE CORRECTED LOAD CLACS FOR ROUTE
 CHOSEN INCLUDE THE CORRECTED PANEL SCHEDULES ANDS
 WIRINGS.