| Plan Review Notes For Permit 13101110 |
| Permit Number |
13101110 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-03 09:18:34 | ON THE FIRST REVIEW OF THE PLANS, THE FOLLOWING | | | DEFICIENCIES WERE NOTED: | | | 1. RELOCATE THE SMOKE DETECTORS AWAY FROM THE CENTER OF | | | THE ROOM IN ANTICIPATION OF CEILING FANS. | | | 2.SHOW SEPARATION BETWEEN UNIT 1 AND THE BASEMENT. | | | 3. THERE IS AN A/C UNIT INSIDE THE BATHROOM OF UNIT 3. | | | 4. AS PER FBC-R 303.8,MINIMUM HEATING IS REQUIRED; NO | | | MENTION OF WHICH IS ADDRESSED. IF THE WINDOW A/C UNITS | | | ARE REVERSIBLE, PLEASE STATE SO AND CORRECT THE | | | INDIVIDUAL LOAD CALC ACCORDINGLY. | | | 5. AS PER NEC 210.52(F), A LAUNDRY CIRCUIT SHALL BE | | | PROVIDED IN EACH UNIT UNLESS COMMON LAUNDRY FACILITIES | | | ARE ON PREMISES. AGAIN, CORRECT THE DRAWINGS AND THE | | | LOAD CALCS AND PANEL SCHEDULES ACCORDINGLY. IF COMMON | | | LAUNDRY FACILITIES ARE BEING IMPLEMENTED, ADDRESS SO | | | AND MAKE THE NECESSARY CHANGE TO THE HOUSE PANEL AND | | | LOAD CALCS. | | | 6. FOR LIFE SAFETY, MINIMUM LIGHTING SHALL BE PROVIDED | | | IN THE ATTIC. | | | 7. DUE TO THE MISSING LOADS, PROPER LOAD CALCS ARE | | | IMPOSSIBLE. PROVIDE CORRECTED LOAD CLACS FOR ROUTE | | | CHOSEN INCLUDE THE CORRECTED PANEL SCHEDULES ANDS | | | WIRINGS. |
|