| 2013-12-14 09:27:39 | PLAN DENIED | | | 1) CFM ON THE PLAN DO NOT MATCH THE CEILING OUTLET | | | SCHEDULE. | | | 2) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 | | | VENTILATION RATES | | | 2010 FBC (M) | | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR 2010 FBC (M). | | | SHOW | | | DUCT DETECTORS ON PLAN. | | | 4) PROVIDE ENERGY CALCULATIONS WITH THE PLAN. PER | | | SECTION | | | 603.2 DUCT SIZING 2010 FBC (M) | | | 5) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | 2013-12-12 10:16:38 | RETURNED TO BIN B25 | | | |
|