2013-12-14 09:27:39PLAN DENIED
 1) CFM ON THE PLAN DO NOT MATCH THE CEILING OUTLET
 SCHEDULE.
 2) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3
 VENTILATION RATES
 2010 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPPLY AIR 2010 FBC (M).
 SHOW
 DUCT DETECTORS ON PLAN.
 4) PROVIDE ENERGY CALCULATIONS WITH THE PLAN. PER
 SECTION
 603.2 DUCT SIZING 2010 FBC (M)
 5) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER