| Plan Review Notes For Permit 13101093 |
| Permit Number |
13101093 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-21 15:00:47 | 721 VILLAGE BOULEVARD #107E | | | PERMIT #13101093 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT | | | DOORS WITH EXIT SIGNS. | | | | | | GENERAL: TOTAL OCCUPANT LOAD DOES NOT APPEAR TO INCLUDE | | | THE BOOTH SEATING CALCULATED AT 1 PER 24-INCHES. | | | | | | SHEET 2.1E: THERE APPEARS TO BE INSUFFICIENT EMERGENCY | | | LIGHTING IN THE KITCHEN AREA AND MAIN SEATING AREA. | | | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM | | | OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL | | | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE | | | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT | | | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, | | | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF | | | EGRESS AT FLOOR LEVEL. | | | | | | SHEET 3.0M: PROVIDE DUCT SMOKE DETECTORS FOR AIR FLOWS | | | ABOVE 2,000 CFM. | | | | | | GENERAL: PLANS DO NOT INDICATE A FIRE ALARM OR FIRE | | | SPRINKLER SCOPE OF WORK. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|