| Plan Review Notes For Permit 13101080 |
| Permit Number |
13101080 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-30 18:49:13 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE MOISTURE SURVEY FOR THE | | | ROOF. CI | | | | | | 2) THE UPLIFT PRESSURES SPECIFIED APPEAR TO BE LOW FOR | | | A BUILDING LOCATED IN EXPOSURE CATEGORY D IN A 170 MPH | | | VULT WIND SPEED WITH A MEAN ROOF HEIGHT OF 90 FT. | | | SUBMIT TWO SIGNED AND SEALED SETS OF CALCULATIONS THAT | | | SHOW HOW THE UPLIFT PRESSURES FOR THE LOW SLOPE ROOF | | | WERE DETERMINED. | | | | | | 3) SUBMIT TWO SETS OF FIELD WITHDRAWL RESISTANCE TEST | | | RESULTS FOR THE ROOF IN ACCORDANCE WITH TAS 105 AS | | | REQUIRED BY LIGHTWEIGHT CONCRETE DECK SYSTEM LIMITATION | | | NUMBER 1 ON PAGE 39 OF NOA #13-0409.7. | | | | | | 4) SUBMIT CALCULATIONS FOR THE REQUIRED FASTENER | | | RESISTANCE VALUE FOR THE MAXIMUM DESIGN PRESSURE VALUE | | | OF -75 PSF OF THE SELECTED SYSTEM. IF THE WITHDRAWL | | | RESISTANCE VALUES ARE LESS THAN THE VALUES REQUIRED BY | | | THE SPECIFIED SYSTEM, SUBMIT REVISED RAS 117 | | | CALCULATIONS THAT UTILIZE THE WITHDRAWL VALUES OF THE | | | TESTING. SEE GENERAL LIMITATION #6 ON PAGE 39 OF THE | | | NOA. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|