| 2014-03-18 12:52:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FROM PREVIOUS LIST #2: | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE ROOF, FAC9N-3. PRODUCT APPROVAL TO BE REVIEWED | | | PRIOR TO SUBMITTAL, FBC 107. | | | | | | 3RD REVIEW: MY APOLOGIES THAT THIS COMMENT WAS NOT | | | CLEAR. REVIEW IS TO BE DONE BY DESIGNER OF RECORD | | | (ARCHITECT) PRIOR TO SUBMITTAL TO THE BUILDING | | | DEPARTMENT. | | | | | | 2. "METAL ROOF" IS SPECIFIED ON THE PLAN. SEE FBC | | | 1507.4.2; 1/4" PER 12" IS ACCEPTABLE FOR STANDING SEAM. | | | 1/2" PER 12" REQUIRED FOR LAPPED, NON SOLDERED SEAM | | | METAL ROOFS WITH APPLIED LAP SEALANT. IF A STANDING | | | SEAM IS NOT PROPOSED, REVISE PITCH. | | | | | | 3RD REVIEW: TWO SETS REQUIRED FBC 107. MINIMUM SLOPE IS | | | 2:12 FOR THIS PRODUCT. PLEASE CORRELATE WITH PLAN WHICH | | | SPECIFIES 1/4" PER 12". | | | | | | |
|