| Plan Review Notes For Permit 13101072 |
| Permit Number |
13101072 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-01-16 20:27:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE ROOF, FAC9N-3. PRODUCT APPROVAL TO BE REVIEWED | | | PRIOR TO SUBMITTAL, FBC 107. | | | | | | 2. "METAL ROOF" IS SPECIFIED ON THE PLAN. SEE FBC | | | 1507.4.2; 1/4" PER 12" IS ACCEPTABLE FOR STANDING SEAM. | | | 1/2" PER 12" REQUIRED FOR LAPPED, NON SOLDERED SEAM | | | METAL ROOFS WITH APPLIED LAP SEALANT. IF A STANDING | | | SEAM IS NOT PROPOSED, REVISE PITCH. | | | | | | |
|