Plan Review Notes
Plan Review Notes For Permit 13101059
Permit Number 13101059
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-30 15:40:44THOUGH NEC 550.33(B) REQUIRES THAT THE MINIMUM
 SERVICE/FEEDERS FOR THE LOTS BE A MINIMUM OF 100 AMP,
 THIS CAN BE CONSIDERED A LEVEL 1 ALTERATION AND UNDER
 THE FBC-EXISTING SECTION 608.1.1 EXISTING WIRING &
 EQUIPMENT UNDERGOING REPAIR CAN BE REPLACED WITH LIKE
 MATERIAL.
2013-10-30 14:47:01PER EC TO SUSAN, THE PREMISES ARE W/O POWER. I CALLED
 THE EC TO CONFIRM THE STATUS BUT WAS UNABLE TO MAKE
 CONTACT. I LEFT A MESSAGE FOR A RETURN PHONE CALL.