| 2013-10-30 15:40:44 | THOUGH NEC 550.33(B) REQUIRES THAT THE MINIMUM | | | SERVICE/FEEDERS FOR THE LOTS BE A MINIMUM OF 100 AMP, | | | THIS CAN BE CONSIDERED A LEVEL 1 ALTERATION AND UNDER | | | THE FBC-EXISTING SECTION 608.1.1 EXISTING WIRING & | | | EQUIPMENT UNDERGOING REPAIR CAN BE REPLACED WITH LIKE | | | MATERIAL. | | 2013-10-30 14:47:01 | PER EC TO SUSAN, THE PREMISES ARE W/O POWER. I CALLED | | | THE EC TO CONFIRM THE STATUS BUT WAS UNABLE TO MAKE | | | CONTACT. I LEFT A MESSAGE FOR A RETURN PHONE CALL. |
|