| 2013-11-18 12:50:09 | MECHANICAL PLAN REVIEW |
| | PERMIT: 13101054 |
| | ADD: 1781 PALM BEACH LAKES # W243 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 CONTACT KARI NEVELLE |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON./ NOV. 18/ 2013 |
| | |
| | ACTION: MECHANICAL PROVISO |
| | MECHANICAL APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) 2010 FLORIDA BUILDING CODE-MECHANICAL 606.2.1 SUPPLY |
| | AIR SYSTEMS. |
| | SMOKE DETECTORS SHALL BE INSTALLED IN SUPPLY AIR |
| | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM |
| | (0.9 M3/S) IN THE SUPPLY AIR DUCT. |
| | |
| | |