| 2013-11-14 17:03:41 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. WITHOUT THE STEEL, IT IS NOT CLEAR HOW THE BLOCK | | | INFILL WILL RESIST WIND LOADS FBC 2010 RESIDENTIAL 301. | | | EITHER PROVIDE CALCUATIONS OR PROVIDE PLANS WHICH ARE | | | PREPARED BY A DESIGN PROFESSIONAL (ARCHITECT OR | | | ENGINEER). INCLUDE WIND DESIGN CRITERIA (FBC 2010 | | | RESIDENTIAL 301). | | | | | | | | | |
|