| 2013-11-18 14:10:17 | ****CORRECTIONS**** |
| | REVIEW OF RESUBS DATED 11/8 AND 11/13 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | A PHOTOGRAPH OF A FLOOR PLAN WAS PROVIDED. IT APPEARS |
| | THAT EMERGENCY MEANS OF ESCAPE AND RESCUE IS NOT |
| | APPLICABLE. PLEASE PROVIDE TWO LEGIBLE PLANS WITH THE |
| | INFORMATION CONTAINED ON THE PHOTOGRAPH, FBC 107. |
| | |
| | 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM |
| | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) |
| | |
| | BASED ON THE PHOTOGRAPHS PROVIDED, THE AFFECTED WINDOWS |
| | ARE A PART OF THE BUILDING ENVELOPE. IMPACT PROTECTION |
| | IS REQUIRED AS THESE WINDOWS ARE NOT INDOORS BUT A PART |
| | OF THE OUTDOOR BUILDING ENVELOPE AND ARE SUBJECT TO |
| | PRESSURES AS WELL AS DEBRIS. |
| | |
| | 3. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE |
| | REQUIREMENTS CAN BE DETERMINED FBC 1609. |
| | |
| | NOT ADDRESSED. |
| | |
| | 4. ADDRESS ON PLAN IS INCORRECT. PLEASE REVISE. (1800 |
| | VISTA DELLAGO) |
| | |
| | NOT ADDRESSED. |
| | |