2013-11-19 15:09:16BUILDING PLAN REVIEW
 PERMIT: 13100981
 ADD: 1781 PALM BEACH LAKES BLVD # W213
 CONT: TO BE DETERMINED
 TEL: (561)
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 06/2013
 ACTION:BUILDING PROVISO
  
 1) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF BOTH
 THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) PLANS RED LINED, SHEETS A2& E1, ONLY ONE EXIT IS
 REQUIRED FOR THE SALES AREA FLOOR, THE 2ND EXIT NOT
 REQUIRED FOR THE PUBLIC THROUGH THE STOCK ROOM, 2010
 FBC-B TABLE 1021.2
 MERCANTILE < 50 OCCUPANTS & TRAVEL DISTANCE OF 75 FEET.
 THE EXIT LIGHT RED LINED TO THE STOCKROOM SIDE OF
 DOORWAY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]