2013-12-06 09:32:45700 SOUTH ROSEMARY AVENUE - #104
 PERMIT #13100977
 MASTER #13030406
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CLOSELY SPACED SPRINKLERS ARE NOT PERMITTED TO PROTECT
 GLASS WALLS OR GLASS DOORS (ONLY IN ATRIA). THE TYCO
 WINDOW SPRINKLER IS THE ONLY SPRINKLER CURRENTLY TESTED
 AND LISTED TO PROTECT GLASS SIDELIGHTS.
  
 TYCO WINDOW SPRINKLERS: IF THE DESIGN INTENT IS TO USE
 TYCO WINDOW SPRINKLERS TO ACHIEVE A FIRE RATED
 SEPARATION, THE SPRINKLERS MUST BE INSTALLED ACCORDING
 TO THE UL LISTING DATA AND SHALL WET THE ENTIRE GLAZING
 SURFACE. SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE
 DOORS OR WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW
 HORIZONTAL WINDOW MULLIONS AND REQUIRE THE GLASS
 CURTAIN WALL TO BE ATTACHED TO A THREE FOOT HIGH PONY
 WALL TO KEEP COMBUSTIBLE MATERIALS AT LEAST TWO INCHES
 AWAY FROM THE GLAZING. PAY SPECIAL ATTENTION TO THE
 GLAZING ASSEMBLY AS THE SPRINKLER POSITIONING VARIES
 FOR BUTT-GLAZED INSTALLATIONS COMPARED TO VERTICAL
 MULLION INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A
 DEPTH THAT PREVENTS COLD SOLDERING OF ADJACENT
 SPRINKLERS. THE SPRINKLER DESIGN SHOULD INDICATE WHICH
 WINDOW SPRINKLER MODEL WILL BE USED (HORIZONTAL
 SIDEWALL OR PENDENT VERTICAL SIDEWALL).
  
 ENTRY VESTIBULE #112 HAS A SSP LOCATED MORE THAN 7'-6"
 FROM TWO WALLS. ADD A SPRINKLER OR USE AN EXTENDED
 COVERAGE SPRINKLER TO PROVIDE ADEQUATE COVERAGE.
  
 CLEAR VEGETATION AROUND EXISTING FIRE DEPARTMENT
 CONNECTION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730