| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | CLOSELY SPACED SPRINKLERS ARE NOT PERMITTED TO PROTECT |
| | GLASS WALLS OR GLASS DOORS (ONLY IN ATRIA). THE TYCO |
| | WINDOW SPRINKLER IS THE ONLY SPRINKLER CURRENTLY TESTED |
| | AND LISTED TO PROTECT GLASS SIDELIGHTS. |
| | |
| | TYCO WINDOW SPRINKLERS: IF THE DESIGN INTENT IS TO USE |
| | TYCO WINDOW SPRINKLERS TO ACHIEVE A FIRE RATED |
| | SEPARATION, THE SPRINKLERS MUST BE INSTALLED ACCORDING |
| | TO THE UL LISTING DATA AND SHALL WET THE ENTIRE GLAZING |
| | SURFACE. SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE |
| | DOORS OR WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW |
| | HORIZONTAL WINDOW MULLIONS AND REQUIRE THE GLASS |
| | CURTAIN WALL TO BE ATTACHED TO A THREE FOOT HIGH PONY |
| | WALL TO KEEP COMBUSTIBLE MATERIALS AT LEAST TWO INCHES |
| | AWAY FROM THE GLAZING. PAY SPECIAL ATTENTION TO THE |
| | GLAZING ASSEMBLY AS THE SPRINKLER POSITIONING VARIES |
| | FOR BUTT-GLAZED INSTALLATIONS COMPARED TO VERTICAL |
| | MULLION INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A |
| | DEPTH THAT PREVENTS COLD SOLDERING OF ADJACENT |
| | SPRINKLERS. THE SPRINKLER DESIGN SHOULD INDICATE WHICH |
| | WINDOW SPRINKLER MODEL WILL BE USED (HORIZONTAL |
| | SIDEWALL OR PENDENT VERTICAL SIDEWALL). |
| | |
| | ENTRY VESTIBULE #112 HAS A SSP LOCATED MORE THAN 7'-6" |
| | FROM TWO WALLS. ADD A SPRINKLER OR USE AN EXTENDED |
| | COVERAGE SPRINKLER TO PROVIDE ADEQUATE COVERAGE. |
| | |
| | CLEAR VEGETATION AROUND EXISTING FIRE DEPARTMENT |
| | CONNECTION. |
| | |