| 2013-11-13 14:39:09 | 700 SOUTH ROSEMARY AVENUE - #104 | | | PERMIT #13100977 | | | MASTER #13030406 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PERMIT APPLICATION INDICATES A VALUE OF $12,750 FOR | | | 226 SPRINKLERS. THIS VALUE IS LOW. THE TOTAL PERMIT JOB | | | VALUE NEEDS TO INCLUDE MATERIALS AND LABOR. PROVIDE | | | SIGNED COPY OF CONTRACT. | | | | | | PRODUCT DATA SUBMITTED IS FOR RESIDENTIAL STYLE | | | SPRINKLERS (TYCO - SIN 3596). | | | | | | PLANS ARE NOT TO SCALE. | | | | | | NO SPRINKLER PROTECTION PROVIDED BELOW MONUMENTAL | | | STAIR. | | | | | | PROVIDE 18" DEEP DRAFT STOPS AND CLOSELY SPACED | | | SPRINKLERS TO PROTECT FLOOR OPENING FOR MONUMENTAL | | | STAIR. | | | | | | MAY NEED TO PROVIDE CORROSION-RESISTANT SPRINKLERS FOR | | | SAUNAS AND WET CORRIDOR. SUBMIT PRODUCT DATA. | | | | | | NO SPRINKLER PROTECTION SHOWN IN NEW ENTRY VESTIBULE | | | #112 OR EXISTING ELEVATOR PIT #110. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|