Plan Review Notes
Plan Review Notes For Permit 13100968
Permit Number 13100968
Review Stop E
Sequence Number 1
Notes
Date Text
2013-11-20 19:06:31ACCORDING TO YOUR OWN LOAD CALCS, YOU ARE GOING TO BE
 PLACING A 136 AMP LOAD ON A 100 AMP PANEL. CORRECT LOAD
 OR ADJUST THE FEEDER TO ACCOMMODATE THE ADDED LOAD.
  
 SENT TO SH DESK