| 2013-12-17 16:04:35 | 6651 NORTH JOG ROAD - POWER BLOCK | | | PERMIT #13100958 | | | MASTER #12040748 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVISO - SUBMIT REVISION | | | | | | STANDPIPE DESIGN: SEVERAL LOWER LEVEL 1-1/2" HOSE | | | VALVES APPEAR TO HAVE PRESSURES THAT WILL EXCEED 100 | | | PSI. PER NFPA 14 SECTION 7.2.3.1, WHERE THE RESIDUAL | | | PRESSURE AT A 1-1/2" OUTLET ON A HOSE CONNECTION | | | AVAILABLE FOR TRAINED PERSONNEL USE EXCEEDS 100 PSI, AN | | | APPROVED PRESSURE-REGULATING DEVICE SHALL BE PROVIDED | | | TO LIMIT THE RESIDUAL PRESSURE TO 100 PSI. ALSO PER | | | NFPA 14 SECTION 7.2.3.2, AN APPROVED | | | PRESSURE-REGULATING DEVICE SHALL BE PROVIDED TO LIMIT | | | STATIC AND RESIDUAL PRESSURES AT THE OUTLET OF THE HOSE | | | CONNECTION TO 100 PSI FOR 1-1/2" HOSE CONNECTIONS | | | AVAILABLE FOR TRAINED PERSONNEL USE AND 175 PSI FOR | | | OTHER HOSE CONNECTIONS. | | | | | | TO AVOID PRESSURE REGULATING DEVICES I WOULD RECOMMEND | | | A TRUE CLASS I STANDPIPE SYSTEM (2-1/2 FDVS ONLY) AND | | | ELIMINATE THE 1-1/2" FDVS WITH HOSE AND REEL BECAUSE | | | FIRE DEPARTMENT PERSONNEL WILL NOT USE THIS EQUIPMENT. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | |
|